SunLogic Electrical Appliance Limited

home products Uninterruptible Power Supply Double Conversion / Online & Sine Wave UPS

Double Conversion / Online & Sine Wave UPS

Product Details:

Phase Single Phase
Type On-line
Certification CE & ISO9001
Place of Origin Guangdong, China
Brand Name VMARK
Model Number LS-5KVA~10KVA

Payment & Shipping Terms:

Minimum Order Quantity: 5 Piece/Pieces
Delivery Time: 30~40 days
Payment Terms: L/C,T/T
Supply Ability: 35000 Piece/Pieces per Month

Detailed Product Description


Model No.LS-1KVALS-2KVALS-3KVALS-6KVALS-10KVA
Rated Power700W1400W2100W4200W7000W
INPUTNominal Voltage(115--300)VAC (Idle Load)/
(165--300)VAC (Full Load)
(176--276)VAC
Frequency(46.5--55)Hz
Power Factor≥0.90
Current Max.6A12A16A30A47A
PhasesSingle Phase+N+GND
OUTPUTVoltage220/230/240±2%VAC
FrequencySynchronous with Input Frequency(Utility Mode)/
50±0.2%Hz(AC Frequency exceed 46~54Hz)
50±0.2%Hz(Battery Mode)
Output WaveformTrue Sine Wave
Harmonics 
Distortion
<3% (Linear Load,Full Load)/
<5%(Non-linear Load) 
Crest Factor3:1
Power Factor0.7
BATTERYTypeSealed Lead-Acid, Maintenance-free
DC Voltage36VDC96VDC240VDC
CapacityDepending on the external battery
Back-up Time
(Half/Full Load)
Charging Voltage41VDC110VDC275VDC
Charging Current5-10A
Typical 
Recharge Time
≤8Hours,Charging Up to 90%
Audible
Alarm
Battery DischargeBeeping sound every 4 seconds after utility power fails
Beeping sound every second if battery approaches final discharge
Overload 
Protection
Continuous beeping
FaultContinuous beeping
PROTECTIONOverload 
Protection
Overload 110%~150%: transfer 
to Bypass after 1Mins, 
Overload above 150%: trandfer 
to Bypass after 30S

Overload 110%~150%: transfer 

to Bypass after 10Mins, 
Overload above 150%:transfer 

to Bypass after 1Min

Low Voltage 
Protection
Automatically shutdown
Tempreture 
Protection
Automatically Transfer to Bypass while Inner Tempreture of UPS>80
Short Circuit
Protection
Automatically Cut Off the Output & Continuous Beeping
UPS AbnormalAutomatically Transfer to Bypass
Transfer
Time
AC to DC0ms
Inverter to Bypass< 4ms
Total Efficiency≥90%
IndicatorsLCD
VFD/LCD Indicator StatusInput/Output Voltage,Frequency,Output Power,
Battery,Utility,Inverter,Overload,Fault,Bypass
Communication PortRs232/USB
InterfaceMonitor of Utility Fault,Power Failure,
Battery,UPS Statu Indicator etc.
Software Function1.Anlysis of Power Status, 2.Timing Controlling, 3.Monitor UPS,
4.Execute UPS Self-diagnosis, 5.Automatic Save
Operating Temperature0~40
Relative Humidity20% ~ 90% non-condensing
Noise< 45dB< 55dB
Dimension(mm)145*400*220192*460*340192*460*340720*570*260720*570*260
Net Weight(Kg)7.50 13.50 14.00 35.00 38.00 

Double Conversion / Online & Sine Wave UPS Double Conversion / Online & Sine Wave UPS

Send your message to this supplier
« Prev Product 1 2 3 4 5 6 7 ... Next Product »

Other Products from this Supplier

Company Info

SunLogic Electrical Appliance Limited
[China]
[Verified Member]

City: Zhongshan
Province/State: Guangdong
Country/Region : China

Business Type:Manufacturer

View Contact Details